Performance Analysis of Three-Phase Shunt Active Power Filter for Harmonic Mitigation
Samson Dauda Yusuf, Abdulmumini Zubairu Loko, Jibrin Abdullahi, Aminu Alhaji Abdulhamid
Asian Journal of Research and Reviews in Physics · pp. 7–24 · Published 17 Oct 2022
10.9734/ajr2p/2022/v6i3118Abstract
Aims: To carried out performance analysis of a shunt active power filter (SAPF) for harmonics mitigation. Study Design: Experimental design through simulation studies using P-Q Theory and proportional integral controller. Place and Duration of Study: Department of Physics, Nasarawa State University Keffi, main campus, Nigeria, between October 2020 and September 2021. Methodology: Primary and secondary data were obtained using AVO Digital Multimeter and manufacturers’ datasheets from Schneider electric website to capture required system parameters, SAPF was designed using a Voltage Source Inverter model to represent the Three-Phase source, and P-Q Theory with PI Control was used for reference current extraction. The SAPF was modeled, designed and simulated using MATLAB-Simulink and analyzed under different nonlinear load conditions and harmonic spectrum to achieve low Total Harmonic Distortion (THD). Results: The THD in the unbalanced system voltages before the application of SAPF was found to be 12.6%, 11.4% and 11.2%, while after the application of SAPF was 2.2%, 2.5% and 2.5% for phase voltages a, b and c respectively. The grid currents indicated THD of 27.2%, 30.9% and 31% before application of SAPF and 2.2%, 2.2% and 2.1% after application. Conclusion: The use of non-linear loads; has adverse effects on the quality of electric power as well as phase voltage and frequency waveforms. The use of SAPF is of vital importance in improving electric power quality for reliable power supply and quality service delivery.
Cited by 3
Minh Ly Duc, Lukas Hlavaty, Petr Bilik · Energies · 2023
Tianhao Hou, Yunhao Jiang, Zishuo Cai · Energies · 2024
Showing 2 of 3 known citations — external sources report more than can currently be individually listed.
Related research
- PSO Enhanced and Deep ANN Control for Voltage Regulation and Harmonic Mitigation in Electrical Distribution Networks — shares topic coverage
- A Design and Mathematical Modeling of the Novel L(LCL)₃ Hybrid Low-Pass Filter for Power Grid-Connected Solar PV Systems — shares topic coverage
- A Comparative Analysis of SIMC-PID with Other Conventional Techniques for Automobile Vehicle Air Conditioning System Control — shares topic coverage
Article metrics
Real usage data collected on this platform.
0
Page views
0
PDF downloads
0
Outbound clicks
3
Citations
Views by country
Approximate, from request IP at view time — not citizenship or institution. Countries with fewer than 5 views are grouped as "Other".
No views recorded yet.
Traffic sources
Referring site, by host.
No traffic recorded yet.
Views and downloads exclude known bots/crawlers. Citations combines this platform's own DOI-resolved index with each external source's own reported total — see Cited by above for individually listed citing works. Last refreshed 0 seconds ago.